OFFSET

RISERUN36.9°
CENTER TO CENTER
Rise
in
Run
in
Wall0.042 inStandard
Using unverified sample bender data. These specs are approximate starting points. Verify deduct, take-up, and radius against your actual bender shoe before trusting these marks.
Mark 1
24 1/2in
Mark 2
55 1/8in
Angle
36.9°
Status
Multiplier
1.67
Shrink
3 11/16 IN
Tolerance
±1/16 IN
Formula - assumptions
tan(angle) = rise / run → angle = 36.87°
Practical angle = 36.86989764584402° (multiplier 1.67)
Distance between bends = rise / sin(angle) = 18.375 / 0.600 = 30.625 in
Shrink (conduit length compensation) ≈ 3.675 in
  (from standard field shrink table: 0.2000 in per inch of rise)

All calculations are based on center-to-center of conduit.